Novel Fault Phase Selector for High Voltage Transmission Line Protective Relaying Based on Boundary Conditions of Three Sequence Voltages
Xu Qingqiang1£¬2 £¬Suonan Jiale1£¬Yang Lifan3 £¬Mao Peng2 £¬Du Xiaogong4
(1.School of Electrical Engineering£¬Xi'an Jiaotong University£¬Xi'an 710049£¬China£»2.Jiangsu Electric Power Research Institute Corporation Limited£¬Nanjing 210036£¬China£»3.Shanghai AREVA Electric Power Automatization Corporation Limited£¬Shanghai 201315£¬China£»4. Yantai DongFang Electronic Information Industry Corporation Limited£¬Yantai 264001£¬China)

Abstract£ºA novel phase selector is proposed for high voltage transmission lines.When a grounding fault occurs£¬three regions can be judged by the phases¡Mangle between the zero sequence and negative sequence components of the current. Each region contains a single phase ground or two phases ground with short fault.The positive£¬ negative and zero sequence voltages of fault point belonging to the two ground faults can be calculated. Then the fault phase can be selected by judging whether these voltages of either fault are concerned with the criteria or not. The selector proposed has excellent performance under high¡Mresistance ground¡Mfault conditions to avoid the mal¡Moperation during power swing.The difference of system cases and the inequality between the positive sequence and negative sequence impedance of the system have no effect on the selector£¬and the accuracy and effectiveness are verified with realª²time digital simulator.
Keywords£ºpower system£»transmission line protection£»oscillation£»fault phase selector