| ¡¡ Suppression of Transient Ground Potential Rise
in Gas Insulated Substation Abstract:Based on analyzing the generating reasons of temporary ground potential rise
(TGPR),a calculation model is suggested to calculate TGPR with electro-magnetic transient
program (EMTP).The results show that TGPR is higher enough to damage the adjacent
equipment connected with gas insulated substation (GIS).To prevent the detrimental TGPR,it
is suggested that line-type metal-oxide arrester is adopted to suppress the very fast
transient overvoltage (VFTO),and ZnO disc to improve the connection between GIS and
adjacent equipment,and the lower residual voltage of ZnO disc,the better suppression
effect on VFTO and TGPR.A site test of TGPR in a domestic 550 kV GIS is carried out.The
waveform of site test coincides with the calculated one very well. |
|