| 第36卷 第7期 | 西 安 交 通 大 学 学 报 | Vol.36 No7 |
| 2002年7月 | Journal of Xi'an Jiaotong Universtity |
Jul. 2002 |
Experimental Study on the Thermosiphon Solution Elevation Tubes
with Narrow Slot Channel in Absorption Chiller
Zheng Hongfei,Wu Yuyuan,Zhang Lianying,Jiang Hua,Zhang Jing
(School of Energy and Power Engineering,Xi'an Jiaotong University,Xi'an 710049,China)
![]()
![]()
Abstract:Several thermosiphon solution elevation tubes with narrow slot
channel are specially designed and constructed. The heating and elevating solution
performances of the tubes are measured. The experimental results indicate that the narrow
slot channel tubes have the outstanding characteritstics, such as the low starting
temperature (minmum 68 degrees), wide operation temperature range (68~90 degrees)
and low vacuum requirement (under 10 kPa). Under the conditions of the suitable
section area of the tubes, the elevating solution volume and distilled water yield
increase with the operation temperature. Other factors having influences on the elevating
solution performance of the tubes are also analyzed and discussed.
Keywords:absorption chiller;thermosiphon elevation solution tube;narrow
slot channel