Phase Voltage Measurement on Very Fast Transients in Non-ymmetrical
Three-Phase Enclosed Gas Insulated Substation
Zou Jianhua,Li Cheng,Xu Changchun,Li Yang,Yue Ziding
(System Engineering Institute,Xi'an Jiaotong University,Xi'an 710049 ,China)
![]()
![]()
Abstract: The method to measure the phase voltage on very fast transients
in a non-symmetrical three-phase enclosed gas insulated substation is described. In order
to measure three phases voltage, three capacitive sensors are needed and each capacitive
sensor is coupled with the electric field of (A,B,and C) three phases voltage. The linear
relation between the output of three capacitive sensors and the three phases voltage is
established by a factorial matrix, which is equal to the product of a constant matrix and
the electric coupling coefficient matrix. As a result of the analysis of the electric
coupling coefficient matrix, the dominant electric coupling coefficients are named, which
have an approximate analytic expression. Furthermore, according to characteristic of the
electric coupling coefficient functions, three capacitive sensors are fixed at the
shortest points of phase A, B, and C. Finally, the curves of three phases voltage on very
fast transients in a non-symmetrical three-phase enclosed gas insulated substation bus
model are given and discussed.
Keywords: gas insulated substation (GIS);ver