Simulation on a Liquid-Desiccant Air Conditioning System without
Pump
Zhao Wei1,Zhu Ruiqi2,Kan Yisong3
(1. Department of Material Science Engineering,Anshan Institute of Iron and Steel
Technology, Anshan 114002,China;2. Shcool of Energy and Power Engineering,Xi'an Jiaotong
University;3. China Resources Property Management Limited)
![]()
![]()
Abstract: The models of absorber and bubble pump in a liquid-desiccant
air conditioning system without pump are developted. By simulation, theoretical analysis
is given, and their performances are predicted. This investigation gives a theoretical
base for the system design. For absorber, the appropriate solution and air mass rate is in
a range of 1.0¡«1.5. For bubble pump, it's size is determined by the pressure loss
analysis of solution circulation. The gravitational loss shares 79%, and the friction loss
18%. The heat power of bubble pump should be within the range, in which the mass rate of
elevated solution and the concentration difference of the generated solution synchronously
increase with increasing of the heat power.
Keywords: Liquid-desiccant;air conditioning;water-lithium chloride
solution;bubble pump;absorber